Yokogawa TDLS8200 Probe-Type Laser Gas Analyzer
Measured parameters: O₂ (Oxygen, Gas)
Measurement method: TDLAS Laser Absorption
TDLS8200 is a probe-type tunable diode laser analyzer flange-mounted from one side, measuring without sampling. Sold and serviced in Türkiye by Tetra.
Installation, calibration, spare parts and service in Türkiye come from Tetra; cabinet and panel integration can be done at our İzmir facility.
Technical information
- Measurement principle
- Tunable diode laser absorption spectroscopy (TDLAS)
- Type
- Probe type, one-sided flange
- Sampling
- Not required
TDLS8200 is the probe-type member of the TDLS family. It measures O2, CO, CH4, NH3 and HCl by near-infrared absorption; in the multiple model, two laser systems measure O2 with CO and/or CH4 together. The company's spectrum area method is less affected by side gases than 2f wavelength modulation and includes temperature and pressure correction.
Installation and operation
- No need for two opposing flanges, light alignment or cross-wiring; measuring area 0.5 m.
- Probe, flow cell and reflector type options are available; the reflector type allows pipes of 0.25-0.5 m diameter.
- Blaster purge function for dusty processes; in a boiler application, O2 and CO response time is stated as 2 seconds.
- Trace levels monitored thanks to a reference cell; HART, 7.5-inch HMI and 50-day trend logging.
- SIL 2 compliant; SIL 3 with two instruments.
Choosing TDLS8200
Active compensation can be used in processes with fluctuating pressure and temperature. Besides boiler combustion control, oxygen monitoring in hydrogen-containing environments in chlor-alkali electrolysis and methane safety at chemical plants are sample applications.
Tetra selects the probe length and configuration according to boiler or pipe dimensions and directs the single-flange mounting on site. Commissioning the blaster purge line and verifying the measurement with reference gas are within the scope of service; because no filter or pump diaphragm is required, maintenance visits are kept short.
Spare parts and consumables
Write to us for spare parts and consumables; the Tetra service team supplies and replaces the right original parts for your instrument.
Ask about spare parts →Products from Yokogawa
Let's choose the right product together
Tell us about your application; we will recommend the right model and configuration for the measuring point, process conditions and regulations.