SENTRY TRW Single-Helix Sample Cooler
The SENTRY TRW single-helix cooler cools low-pressure boiler water samples; sold and serviced in Türkiye by Tetra.
Installation, calibration, spare parts and service in Türkiye come from Tetra; cabinet and panel integration can be done at our İzmir facility.
Technical information
- Tube (coil) rating
- Up to 2000 psi, 850 °F (138 bar, 454 °C)
- Body rating
- Up to 250 psi, 450 °F (17 bar, 232 °C)
- Surface area
- 0.11 m²
- ASME stamp
- Not available
TRW is a single-helix sample cooler whose small profile fits tight spaces, particularly on or near the boiler. It is suitable for low-pressure boiler water and flows below 1200 cc per minute. The sample flows on the tube side and cooling water on the shell side; the cooled sample is delivered to the laboratory or in-line analysis instruments.
Technical data
- Tube: up to 2000 psi and 850 °F (138 bar, 454 °C).
- Shell: up to 250 psi and 450 °F (17 bar, 232 °C).
- Shell 304/304L; coil 1/4 inch 316/316L stainless steel; no alternative material offered.
- Heat transfer surface 0.11 m²; no ASME stamp.
- The helical design reduces cooling water consumption.
For work with higher pressure or ASME requirements, TLR, WSW, FSR or FLR models from the same family are considered.
Choosing TRW
This model is specified for low-pressure boiler water and has no ASME-stamped version. Applications requiring an ASME stamp or high flow need a different single-helix model.
Tetra checks whether TRW is sufficient by looking at the flow of the boiler water sample line, and otherwise directs you to a suitable model. Mounting, cooling water connection and later spare parts supply are carried out locally.
Spare parts and consumables
Write to us for spare parts and consumables; the Tetra service team supplies and replaces the right original parts for your instrument.
Ask about spare parts →Products from SENTRY Equipment
Let's choose the right product together
Tell us about your application; we will recommend the right model and configuration for the measuring point, process conditions and regulations.